EVSE testersSafe isolationAccessoriesInsulation testingPAT solutionsSocket testingInstallation testingIndustrial testingEnvironmentalTest leads & accessories

Martindale EZ365 Socket, Earth Loop & RCD Tester

MPN: MAREZ365

MPN: MAREZ365

In addition to detecting 28 socket wiring fault conditions and checking mains voltage levels, the EZ365 verifies the earth wiring by carrying out a non-trip earth loop test and indicating its value in 6 discrete ranges from less than 1.7Ω to 500Ω.

A low earth resistance is essential for safety disconnection devices to work properly and prevent electrocution when faults occur. In contrast basic socket testers only indicate the presence of an earth and will do so even when resistance values are dangerously high.

Socket polarity and earth wiring faults are identified by a combination of red LEDs. The 3 LEDs correspond to neutral, earth and live connections to aid fast identification of the source of common faults. A look up chart on the tester provides further fault diagnosis.

The EZ365 also has the capability to check for L-NE polarity swap at the incoming supply and can be used to trip test 30mA RCDs. The polarity swap test detects a serious fault condition that cannot be identified by normal socket testers and is easily activated by using the touch pad on the EZ365.

The EZ365 is an Advanced Socket Tester as defined by the Health & Safety Executive as it indicates earth loop impedance. Advanced Socket Testers offer a simple solution to verifying socket earthing and are commonly used by engineers and technicians prior to servicing and installing mains powered electrical and gas appliances.

Quick & easy testing of mains wiring

Detects 28 fault conditions

Supply polarity check

RCD trip check

Earth loop impedance check

Nominal operating voltage

230V AC rms

Operating frequency

50Hz

Power

from mains socket under test

Non-trip earth loop impedance ranges

0 – 1.7 – 5 – 10 – 100 – 200 – 500Ω

Earth loop threshold accuracy

± (10% + 0.3Ω) *

Voltage low high indication

L=<195V ± 5% H=>270V ± 5%

RCD test current at 195V

30mA

Duration of RCD test current

300ms

Polarity reversal test

L-NE swap at incoming supply

EMC

Conforms to BS EN 61326-1

Warranty

2 Years

Full product specification can be found in the product manual or by contacting our team here

EAN: 5036162187858

EZ165EZ664EZ365
Indicate functional socket
Detect line/neutral reversal
Detect presence of earth
Audible indication
Mains voltage check
Earth loop impedance range
Polarity swap touch test
30mA RCD trip check
Connection via 13A plug
Connection via 4mm leadset
£75.00 (List excl. VAT)
Add to basket

The all-new BZ820-EV for EV socket testing

The optimum first-line tool for checking EV chargers fitted with Type-2 connectors.

Discover the BZ820-EV

Not all socket testers are the same

Martindale’s extensive range of socket testers not only performs the standard functionality tests on an outlet, some can also check the mains level, check for supply Line-Neutral reversal and perform a non-trip earth loop test!

Learn more about Socket testing

Added to basket

Technical support

If you have questions related to Martindale products, please check our FAQ sections on our product pages, where the most common enquiries are answered.

Should you require further help please do not hesitate to contact the Martindale support team using the telephone number or email address below or complete the online form.

+44 (0) 1923 441 717 (Mon-Fri, 8am-5pm)

"*" indicates required fields

This field is for validation purposes and should be left unchanged.
Name*