Martindale VR2250 17th Edition Multifunction Tester with Power Analysis - Martindale 17th Edition Test Equipment Search: 
 
Call 01923 441717

Martindale Electric Company Ltd - Catalog Feed

Manufacturers of Electrical Test Equipment
Home  About Us  News  PAT Training  Calibration  FAQs   Technical Support  Image Gallery  Contact Us 
   » Home » Martindale 17th Edition Test Equipment » Martindale VR2250 17th Edition Multifunction Tester with Power Analysis
Twitter   Facebook
YouTube"   LinkedIn

Martindale VR2250 17th Edition Multifunction Tester with Power Analysis

Click Images to Enlarge

Martindale Order Code: MARVR2250
Print Page   Bookmark this page  
   Buy Now
Martindale Veritest VR2230 17th Edition Multifunction Tester

Martindale Veritest VR2230 17th Edition Multifunction Tester

Martindale Veritest VR2240 17th Edition Multifunction Tester

Martindale Veritest VR2240 17th Edition Multifunction Tester


Product Details

Combined 17th Edition multifunction tester combined with a single phase power analyser and earth resistance tester. The Martindale VR2250 is excellent value for money, incorporating all the required tests for the 17th Edition.

With energy consumption becoming more of a concern to people, the demand for power analysis is growing fast. The Martindale VR2250 will log current & voltage, producing an analysis report from the software package (sold separately).

A flexi clamp adaptor is available, which can be easily clamped around small cables or large busbars, for power readings of up to 2000A.

Key Features of the Martindale Veritest 2250 17th Edition Multifunction Tester

  • Insulation & Continuity Test
  • RCD test up to 500mA, including ramp and auto test
  • Non Trip & High Current Earth Loop Test
  • Earth Resistivity Test (Optional Spike Kit Needed)
  • Single Phase Power Analysis
  • Live Circuit Warning
  • Phase Rotation
  • The Martindale Veritest 2250 is supplied with 3 way lead set & croc clips, mains test lead, batteries, soft carry case & instruction manual.

    Specification

    Continuity
  • AUTO, R+, R-:
          0.01 - 19.99Ω resolution 0.01Ω
          20.0 - 99.9Ω resolution 0.1Ω
  • Timer Mode: 0.01 - 9.99Ω resolution 0.01Ω
  • Test Current: >200mA DC up to 16Ω, 40mA DC from 16Ω to 99.9Ω
  • Open Circuit Test Voltage: 9V
  • Live Circuit Warning: Yes
  • Timer: test duration 10 - 999 seconds
  • Insulation Tests

  • 50V:
          0.05 - 19.99MΩ resolution 0.01MΩ
          20.0 - 49.9MΩ resolution 0.1MΩ
          50.0 - 99.9MΩ resolution 0.1MΩ
  • 100V:
          0.10 - 19.99MΩ resolution 0.01MΩ
          20.0 - 99.9MΩ resolution 0.1MΩ
          100.0 - 199.9MΩ resolution 0.1MΩ
  • 250V:
          0.23 - 19.99MΩ resolution 0.01MΩ
          20.0 - 199.9MΩ resolution 0.1MΩ
          200 - 249MΩ resolution 1MΩ
          250 - 499MΩ resolution 1MΩ
  • 500V:
          0.25 - 19.99MΩ resolution 0.01MΩ
          20.0 - 199.9MΩ resolution 0.1MΩ
          200 - 499MΩ resolution 1MΩ
          500 - 999MΩ resolution 1MΩ
  • 1000V:
          0.90 - 19.99MΩ resolution 0.01MΩ
          20.0 - 199.9MΩ resolution 0.1MΩ
          200 - 999MΩ resolution 1MΩ
          1000 - 1999MΩ resolution 1MΩ
  • Automatic Selection of Measuring Range
  • Open Circuit Voltage: Rated test voltage -0% +10%
  • Short Circuit Current:
          <3.0mA - 500V
          <2.0mA - 50V, 100V, 250V, 1000V
  • Test Current on Load: >1mA @ Vtest across Rload = (1000 x Vtest)Ω
  • Live Circuit Detection: Test inhibit if voltage detected is higher than 30V
  • RCD

  • RCD Types: AC, A
  • Phase to Earth Voltage: 100 - 265V
  • Rated Tripping Current (IΔn): 10mA, 30mA, 100mA, 300mA, 500mA
  • Test Frequency: 50Hz +/- 0.5Hz
  • RCD Tripping Times

  • 1/2 IΔn, IΔn:
          0 - 999ms, resolution 1ms
  • 2 IΔn:
          0 - 200ms general, resolution 1ms
          0 - 250ms selective, resolution 1ms
  • 5 IΔn RCD (*):
          0 - 50ms general, resolution 1ms
          0 - 160ms selective, resolution 1ms
          * for RCD type A 500mA, the MAN x 5 and AUTO tests are not available.
  • Contact Voltage

  • Measuring Range: 25 or 50V, resolution 0.1V
  • Tripping Current for RCD Type A and AC
    RCD with IΔn < 10mA

  • AC: 0.5 - 1.4 IΔn, resolution 0.1IΔn
  • A: 0.5 - 2.4 IΔn
  • RCD with IΔn > 10mA

  • AC: 0.5 - 1.4 IΔn, resolution 0.1 IΔn
  • A: 0.5 - 2 Δn
  • AC Voltage

  • Single Phase: 0 - 265V, resolution 1V
  • 2 or 3 Phase: 0 - 460V, resolution 1V
  • Frequency

  • Range: 15.3 - 99.9Hz, resolution 0.1Hz
  • Line Impedance

  • P-P & P-N:
          0.03 - 19.99Ω, resolution 0.01Ω
          20.0 - 199.9Ω, resolution 0.1Ω
  • PSC: 1 - 999A, 1.0 - 20.0KA
  • Test Voltage:
          P-N 100V - 265V, 50Hz
          P-P 100V - 460V, 50Hz
  • Max Peak Test Current:
          100V, 3.17A, test duration 80ms
          230V, 6.64A, test duration 40ms
          400V, 11.5A, test duration 40ms
  • Phase Earth Impedance (Loop Zs / Ik)>

  • Test Ranges:
          0.03 - 19.99Ω, resolution 0.01Ω
          20.0 - 199.9Ω, resolution 0.1Ω
          200 - 1999Ω, resolution 1Ω
  • PFC: 1 - 999A, 1.0 - 20.0KA
  • Max Peak Test Current:
          100V, 3.17A, test duration 80ms
          230V, 6.64A, test duration 40ms
  • Non Trip Earth Loop Test

  • Measuring Range: 1 - 1999Ω, 1Ω resolution
  • PFC: 1 - 999A, 1.0 - 20.0kA
  • Test Current: 15mA
  • Earth Ground Resistance (with optional spike kit)

  • 0.1Ω - 19.99Ω (0.01Ω resolution)
  • 20.0Ω - 199.9Ω (0.01Ω resolution)
  • 200Ω - 1999Ω (1Ω resolution)
  • Power Analyser Functions

    Active Power

  • 0 - 99.99 (W, KW) MW
  • Reactive Power

  • 0 - 9999 (VAR, kVAR) MVAR
  • Apparent Power

  • 0 - 9999 (VA, kVA) MVA
  • Active Energy

  • 0 - 9999 (Wh) MWh
  • Reactive Energy

  • 0 - 9999 (VARh) MVARh
  • Memory Slots For Saved Tests

  • 999
  • Phase Rotation Test

  • Supplied with: Soft Carry Case, Batteries, User Manual, Mains Test Lead, 3 Way Fused Lead Set.
  • Additional Accessories: Mains Power Supply, 2000A Flexi Clamp, Download Lead, Reporting Software, Earth Spike Kit
  • Application Notes

    Please click the links below to download the application notes in pdf format.

    Building Regulations in addition to Part P

    Where can I get my instruments calibrated?

    Ask a question

       Accessories & Spares For This Product
    Martindale TL63 3 Way Unfused Test Lead Set
    Martindale TL63 3 Way Unfused Test Lead Set
    Martindale TL206 Mains Test Lead
    Martindale TL206 Mains Test Lead
    Martindale Safebreak R2 Socket Adaptor
    Martindale Safebreak R2 Socket Adaptor
    Metrohm FLEX2250 2000A Flexible Current Clamp for the Martindale VR2250
    Metrohm FLEX2250 2000A Flexible Current Clamp for the Martindale VR2250
    Martindale VRSOFT2 Veritest 2250 17th Edition & Power Analysis Software
    Martindale VRSOFT2 Veritest 2250 17th Edition & Power Analysis Software
    Martindale VRTL1 Veritest Download Lead
    Martindale VRTL1 Veritest Download Lead



    Gambica Membership    Martindale Electric - Quality Assured    Martindale Electric - Quality Assured    Achilles Membership    Martindale Electric - Quality Assured Martindale Electric Ltd, Metrohm House, Penfold Trading Estate, Imperial Way,
    Watford, Hertfordshire, WD24 4YY
    © Copyright 1998-2012 Martindale Electric Company Ltd.
    All Rights Reserved. Registered in England No. 3387451.