Product Details
Nothing is more dangerous than trusting a defective voltage indicator to test for a dead circuit. Safe electrical work requires the use of a voltage indicator that has been proved with a proving unit before and after use.
The Martindale VIPD contains the VI137002 voltage indicator and the PD440 proving unit, enabling you to comply with health and safety recommendations for safe working.
Specification
Martindale VI13700/2 Voltage Indicator Specifications
Voltage Ranges
50 - 400V AC/DC
LED Indication
+/-50, 100, 200, 400V
Polarity Indication
from 12V
AC / DC Voltage Detection
Automatic
Range Detection
Automatic
Response Time
<0.1s
Frequency Range
DC, 0 - 65Hz
Test Current
3.5mA max at 400V AC/DC
Duty Ratio
30s ON / 240s Off
Temperature Range
-10°C to +55°C
Humidity
max. 85% rel. H
Altitude
up to 2000m
Overvoltage Category
CAT IV / 600V, CATIII 1000V
Pollution Degree
2
Environmental Protection
IP54
Safety
GS38, BS EN 61010
Weight
approx 130g
Dimensions
approx 205 x 67 x 27
Martindale PD440 Specification
Output Voltage
440V, 50Hz
Operating Temperature
-10°C to +40°C at max 70% RH
Battery
6 x LR6 / MN1500 1.5V alkaline batteries or equivalent
Dimensions
143 x 84 x 50mm
Weight