Product Details
The Martindale EZ150 was the first socket tester to include measurement of earth loop impedance. Conventional socket testers will only indicate the presence of an earth, however if the socket has a dangerously high earth resistance, they will not be able to identify this. Using the EZ150 gives you the peace of mind that not only is the socket wired correctly, but also the earth resistance is within acceptable levels.
Martindale's T-SafeTM technology is incorporated into the EZ150, in order to ensure that RCDs will not trip when the loop impedance check is carried out.
Earth loop measurement, and socket faults, are all indicated with bright, long-life LEDs. This unit should be used as an indicator only and not to provide readings for completion of certificates.
Specification
Mains Supply
230V (50Hz)
Earth Loop Impedance Span
0 - 1.7Ω, 1.7 - 5Ω, 5 to 10Ω, 10 to 100Ω, 100 to 200Ω, 200 to 500Ω
Earth Loop Impedance
+/- 10%, +0.3Ω
Voltage Low Indication
<195V
Voltage High Indication
>270V
Open Earth Indication
>500Ω
Power Consumption
<1.6W
Overvoltage
CAT II, 300V
Housing
Flame retardant ABS
Dimensions
65 x 65 x 50mm
Weight
64g approx