Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test

Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
general image
Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
Martindale EPAT2100 Dual Voltage Manual PAT Tester with Flash Test
general image
Martindale Part No: MAREPAT2100

The simple one button, one test interface for testing both 240V and 110V appliances speeds up testing. It performs the mandatory tests for earth bond and insulation and has the added benefits of run current, run leakage and flash test making it ideal for both routine onsite testing, tool hire checks and workshop service and repair applications. The EPAT2100 is capable of full high current bond testing at 25A and 8A or can be set to 200mA for safe testing of sensitive IT equipment.

It can be powered by a 110V or 240V supply which enables the run current or run leakage test to be performed without the need for connection to an external power source. The TL150 110V adaptor is included to enable connection to a 110V supply.

The Easypat2100 has a built in lead tester for testing IEC power leads and includes all accessories for fast testing of mains extension leads. The lead tester will perform a polarity test and clearly indicates any faults found during the test.

Suitable for onsite PAT testing and workshop applications
Simple one button, one test operation
Fast and easy Class I & Class II appliance testing
Tests both 240V and 110V appliances based on supply voltage
High and low current earth bond tests at 8A, 25A and 200mA
Insulation test at 500V
Extension & IEC lead testing built-in
Run current & leakage tests for full appliance testing
Hipot / Flash testing for tool hire and workshop service & repair applications
Mains powered 110V/240V with instant on
Hard case with storage and removable top

FREE_VC.jpg 


Earth Bond Test
  • Test Currents: 8A AC, 25A AC, +/- 200mA DC (IT Safe)
  • Display Range: 0.00Ω - 1.99Ω

Insulation Resistance

  • Test Voltage: 500V DC
  • Display Range: 0 - 19.9MΩ

Run Current Test

  • Range: 0 - 19.9mA
  • Usable Range: 0 - 13.0A

Earth Leakage Test

  • Range: 0 - 19.9mA

Flash Test

  • Test Voltage: Class I - 1.5kV AC; Class II - 3.0kV AC
  • Display Range: 0 - 19.9mA AC
  • Usable Range: 0 - 3mA (current trip @ 4mA nominal)

Fuse Test

  • Test Voltage: 6V AC Nominal
  • Over range Threshold: 10kΩ nominal
  • Zero Range Threshold: 800kΩ nominal

IEC & Extension Lead Test

  • Earth Continuity: 8A AC, 25A AC
  • Insulation Test: 500V DC
  • Wiring Test: Live, Neutral Continuity & Polarity

How do I test 3 Phase appliances?
You need to use our 3-Phase adaptor leads that allow a single phase PAT tester to carry out safety tests on 3-Phase appliances. Only the basic tests can be performed, i.e. earth bond and insulation tests. Obviously it is not possible to carry out the RUN tests with a single phase PAT tester.

The adaptors you require are as follows:

  • Part number MARTL151: 16A, 4 Pin adaptor
  • Part number MARTL152: 16A, 5 Pin adaptor
  • Part number MARTL153: 32A, 4 Pin adaptor
  • Part number MARTL154: 32A, 5 Pin adaptor
  • It is also advisable to purchase a copy of the IEE Code of Practice, if you haven't already done so.

    Print    Bookmark    Manual     Datasheet   
    general image
    general image
    Metrohm - a Martindale Brand
    Drummond - a Martindale Brand
    Luckins Logo - Martindale is listed in Luckins Live Martindale Electric Co Ltd, Metrohm House, Imperial Park, Imperial Way, Watford, Hertfordshire, WD24 4PP
    Company Registration No: 3387451. © Martindale Electric Co Ltd 1997 - 2017, all rights reserved.
    T: +44 (0) 1923 441 717   F: +44 (0) 1923 446 900   E: sales@martindale-electric.co.uk
    E. & O.E. Privacy Notice | Terms & Conditions | Contact Us